Applications:
These cables are used for the connection of mobile operating equipment, in mines and underground excavations with hazardous environments, in stationary operation, e.g. high-voltage transformers in mining and tunnelling.Flexible cable for energy supply to MV equipment in tunnelling and underground mining applications. Suitable for indoor and outdoor applications.
For the connection of mobile operating equipment, in mines and underground excavations with hazardous environ-ments, in stationary operation, e.g.
high-voltage transformers in mining and tunnelling, which are shifted forward in stages as excavation work progresses, in particular in 10 kV networks and -due to the low capacitance of the cables – in expanded 5 kV networks.The mobility of the cable means it can be laid in containers and can be unwound from these as working operations progress. The phase- concentric earth conductor and the common concentric monitoring shield,
in conjunction with a high-voltage protection circuit, make it possible to monitor the cable for insulation faults and damage resulting from external influences.
Standards Applied
VDE 0250 Part 605
Construction
Conductors: Flexible strandedcopper conductor, class 5 according to DIN VDE 0295.
Insulation: EPR compound type 3GI3.
Electrical Field Control:Inner and outer semiconductive layer ofsemiconductive rubber, for 6 kV outersemiconductive layer only.
Pilot Cores:Stranded copper conductor with EPR insulation.
Earth Conductor: Spiral ofcopper wiresover the outer semi-conductivelayer of the cores.
InnerSheath: PVC compound type YM5.
Monitoring Conductor: Conductive tape serving and overallconcentric Cu wire spinning.
Intermediate Sheath: PVCcompound type YM5.
Armour:Braid of galvanized steel wires.
Outer Sheath: PVC compound type YM5.
Characteristics
Voltage Rating (Uo/U)
3.6/6kV
6/10kV
Test Voltage
3.6/6kV: 11kV
6/10kV: 17kV
Maximum Short Circuit Temperature
+250°C
Maximum Working Temperature on the Conductor
+90°C
Ambient Temperature
Fixed: -40°C to +80°C
Flexed: +5°C to +80°C
Minimum Bending Radius
Fixed: 6 x overall diameter
Flexed: 10 x overall diameter
Maximum Tensile Load*
15N/mm2
Specifications
3.6/6kV
Number of Cores×Nominal Cross Section | Minimium Overall Diameter | Maximum Overall Diameter | Nominal Weight |
No. ×mm² | mm | mm | kg/km |
3×25+3×16/3E+3×2.5ST+UEL | 49.0 | 53.0 | 4190 |
3×35+3×16/3E+3×2.5ST+UEL | 52.0 | 56.0 | 4800 |
3×50+3×25/3E+3×2.5ST+UEL | 55.0 | 59.0 | 5600 |
3×70+3×35/3E+3×2.5ST+UEL | 59.0 | 63.0 | 6650 |
3×95+3×50/3E+3×2.5ST+UEL | 63.0 | 67.0 | 7940 |
6/10kV
Number of Cores×Nominal Cross Section | Minimium Overall Diameter | Maximum Overall Diameter | Nominal Weight |
No. ×mm² | mm | mm | kg/km |
3×25+3×16/3E+3×2.5ST+UEL | 55.0. | 58.0 | 5300 |
3×35+3×16/3E+3×2.5ST+UEL | 58.0 | 61.0 | 5910 |
3×50+3×25/3E+3×2.5ST+UEL | 61.0 | 65.0 | 6790 |
3×70+3×35/3E+3×2.5ST+UEL | 65.0 | 69.0 | 7860 |
3×95+3×50/3E+3×2.5ST+UEL | 68.0 | 73.0 | 9180 |
8.7/15kV
Number of Cores×Nominal Cross Section | Minimium Overall Diameter | Maximum Overall Diameter | Nominal Weight |
No. ×mm² | mm | mm | kg/km |
3×25+3×16/3E+3×2.5ST+UEL | 58.0 | 62.0 | 6810 |
3×35+3×16/3E+3×2.5ST+UEL | 61.0 | 65.0 | 7850 |
3×50+3×25/3E+3×2.5ST+UEL | 64.7 | 68.7 | 9130 |
3×70+3×35/3E+3×2.5ST+UEL | 67.9 | 71.9 | 10750 |
3×95+3×50/3E+3×2.5ST+UEL | 72.4 | 76.4 | 12290 |
12/20kV
Number of Cores×Nominal Cross Section | Minimium Overall Diameter | Maximum Overall Diameter | Nominal Weight |
No. ×mm² | mm | mm | kg/km |
3×25+3×16/3E+3×2.5ST+UEL | 62.3 | 66.3 | 8790 |
3×35+3×16/3E+3×2.5ST+UEL | 65.3 | 69.3 | 9930 |
3×50+3×25/3E+3×2.5ST+UEL | 69.0 | 73.0 | 11360 |
3×70+3×35/3E+3×2.5ST+UEL | 72.2 | 76.2 | 13100 |
3×95+3×50/3E+3×2.5ST+UEL | 76.8 | 80.8 | 14750 |